The SY series actuator must be mounted at or above pipe center line. Not to be installed below horizontal. The results include the actuator losing the NEMA4/water-tight rating and premature failure.
Additional information can be found in the the following link Butterfly Valve Installation
Please contact technical support to discuss further options in non-conforming installations.