The ZIP Economizer can be reset to original factory setting if the software is version 2.0 or higher. This feature is not available on the original software version.
Resetting the ZIP to Virgin Mode
- Press “ESC” until “Monitor Live Conditions” is displayed
- Press “OK”
- Press up arrow once – Firmware will appear
- Press the following 4 keys one at a time in sequence
- OK
- I
- UP
- DOWN
- Reset to virgin push OK resets to factory defaults will be displayed
- Press “OK”
- Settings Menu will be displayed